Specification and requirement
In the United States, Occupational Safety and Health Administration (OSHA) regulations on emergency eyewash and shower station are contained in 29 C.F.R. 1910.151 (c), which provides that “Where the eyes or body of any person may be exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body shall be provided within the work area for immediate emergency use.” However, OSHA regulation is unclear defining what facility is required. From this reason, American National Standards Institute (ANSI) has developed a standard (ANSI/ISEA Z358.1-2014) for emergency eyewash and shower stations, including the design of such stations.
Safety Shower
- The path from the hazard to the safety shower shall be free of obstructions and tripping hazards.
- Water supply should be enough to provide at least 20 gallons per minute of water for 15 minutes (Section 4.1.2, 4.5.5).
- Hand free valve should be able to open within one second and remain open until it is manually closed (Section 4.2, 4.1.5).
- The top of the water column shall not be lower than 82″ (208.3 cm) and no higher than 96″ (243.8 cm) above the surface floor the user is standing on(Section 5.1.3, 4.5.4).
- Center of the water column should be at least 16″ (40.6 cm) away from any obstruction (Section 4.1.4, 4.5.4).
- Actuator should be easily accessible and easily located. It should be no more than 69″ (173.3 cm) above the surface floor the user is standing on (Section 4.2).
- At 60″ (152.4 cm) above the floor, the water pattern should be 20″ (50.8 cm) in diameter (Section 4.1.4).
- If shower enclosure is provided. It should provide 34″ in diameter of unobstructed space (86.4 cm) (Section 4.3).
- Water temperature of safety shower station should be within 60 °F – 100 °F (16 °C – 38 °C).
- Safety shower stations should have highly visible and well lit signage.
Eyewash Station
- The path from the hazard to the Eyewash or Eye/Face wash shall be free of obstructions and tripping hazards.
- Eyewash station shall flush both eyes simultaneously within gauge guidelines (Eyewash gauge detailed in ANSI/ISEA Z358.1-2014) (Section 5.1.8).
- Eye or Eye/Face wash shall provide a controlled flow of water that is non-injurious to the user (Section 5.1.1).
- Nozzles and flushing fluid shall be protected from airborne contaminants (dust covers), and shall not require a separate motion by the operator when activating the equipment (section 5.1.3).
- Eyewashes must deliver 0.4 gpm for 15 minutes, Eye/Face washes must provide 3 gpm for 15 minutes.
- The top of the Eye or Eye/Face wash water flow must not fall below 33″ (83.8 cm) and can be no higher than 53″ (134.6 cm) from the floor surface floor the user is standing on (Section 5.4.4).
- The head or heads of the Eyewash or Eye/Face wash must be 6″ (15.3 cm) away from any obstructions (Section 5.4.4).
- The valve must allow for 1 second operation and the valve shall remain open without the use of the operator’s hands until intentionally closed. (Section 5.1.4, 5.2).
- Manual or automatic actuators shall be easy to locate and readily accessible to the user (Section 5.2).
- Water temperature of Eye or Eye/Face wash station should be within 60–100 °F (16–38 °C).
- Eye or Eye/Face wash stations should have highly visible and well lit signage.
Location
Safety showers and eyewash stations should be within 10 seconds walking distance or 55 feet (appendix B) from the hazard and must be located on the same level as the hazard, so the individual does not have to go up or down the stairs when an accident occurs. Moreover, the path way should be clear and free of obstructions.